Glossary•Equipment

Chiller

An HVAC system that removes heat from a liquid via a vapor-compression or absorption refrigeration cycle.

Full Definition

A Chiller is a machine that removes heat from a liquid (typically water) through a vapor-compression or absorption refrigeration cycle. This chilled liquid is then circulated through heat exchangers to cool air or equipment. Chillers are central to large building cooling systems, producing chilled water that is distributed to air handling units, fan coil units, and other terminal units. Chillers are tracked with properties for cooling capacity, efficiency ratings (COP, EER), refrigerant type, and operational status.

How It Works

CHILLER REFRIGERATION CYCLE Vapor-compression cycle for building cooling CHILLER UNIT EVAPORATOR Absorbs Heat from Water COMPRESSOR Increases Pressure Electric Motor Driven M CONDENSER Rejects Heat to Water EXPANSION VALVE Reduces Pressure LOW P GAS HIGH P GAS HIGH P LIQUID LOW P LIQUID/GAS MIX TO AHUs 42°F Supply FROM AHUs 54°F Return TO TOWER 95°F FROM TOWER 85°F COOLING TOWER Heat Rejection to Atmosphere

The chiller refrigeration cycle

Most building chillers use the vapor-compression cycle. Warm water returning from the building passes through the evaporator, where refrigerant boils at low pressure and absorbs the heat. The compressor raises the pressure and temperature of the refrigerant vapor, and the condenser rejects that heat to outdoor air or to condenser water. An expansion device then drops the pressure so the cycle can repeat.

In a typical comfort cooling plant, the chiller supplies chilled water at around 42 to 45°F, and the water returns roughly 10 to 12°F warmer after passing through air handler and fan coil coils. Absorption chillers do the same job using a heat source such as steam, hot water or natural gas instead of a mechanical compressor.

Main types of chillers

Chillers are usually described by how they reject heat and by the type of compressor they use.

  • Air-cooled chillers reject heat directly to outdoor air with condenser fans. They need no cooling tower and are common in small to mid-size buildings.
  • Water-cooled chillers reject heat to condenser water that is cooled by a cooling tower. They are generally more efficient and are typical in large central plants.
  • Scroll compressors are used in smaller chillers, often several in one unit.
  • Screw compressors cover mid-size capacities.
  • Centrifugal compressors are used in large chillers, including oil-free magnetic bearing designs.
  • Absorption chillers use heat instead of an electric compressor to drive the cycle.

Chiller vs cooling tower vs air handler

These three are often confused because they work together. The chiller makes cold water. Air handlers and fan coil units use that cold water to cool and dehumidify the air supplied to occupied spaces. On water-cooled systems, the cooling tower removes the heat the chiller pulled out of the building, using condenser water that typically returns from the tower at around 85°F on a design day.

Pumps move water through both the chilled water and condenser water loops, and the plant controls decide how many chillers, pumps and tower fans run to meet the load.

Capacity and efficiency

Chiller capacity is rated in tons of refrigeration, where one ton equals 12,000 Btu per hour of heat removal. Efficiency is usually expressed as kW per ton, where lower is better, or as COP or EER, where higher is better.

Part-load ratings such as IPLV, defined in AHRI Standard 550/590, matter because chillers spend most of their operating hours below full load. Minimum efficiencies for new chillers are set by energy codes based on ASHRAE 90.1.

Maintenance and common problems

Chillers are among the most expensive pieces of equipment in a building, so they get close attention. Typical maintenance includes logging temperatures, pressures, amps and approach temperatures, cleaning condenser tubes on water-cooled units (usually annually) with periodic eddy current testing of the tubes, oil and refrigerant analysis, leak checks, cleaning condenser coils on air-cooled units, and checking water treatment, flow switches and safety controls.

Common problems include fouled condenser tubes that raise head pressure and energy use, low refrigerant charge from leaks, low water flow trips, short cycling at low loads, and drifting sensors that cause poor staging. A rising approach temperature, the gap between the leaving water temperature and the refrigerant temperature, is an early sign of fouling or low charge.

In a digital twin such as Syyclops, the chiller's live BMS points, work orders and maintenance history are attached to the same asset, so current readings and past repairs can be reviewed together.

Frequently Asked Questions

What is a chiller in HVAC?

A chiller is a machine that cools water, or a water and glycol mix, using a refrigeration cycle. The chilled water is pumped to air handlers and fan coil units, which use it to cool the air in the building.

What is the purpose of a chiller?

A chiller provides central cooling for large buildings and processes. It removes heat from water at one central plant so cooling can be distributed through piping to many air handlers, fan coils or process loads.

What is the difference between an air-cooled and a water-cooled chiller?

An air-cooled chiller rejects heat to outdoor air with fans and needs no cooling tower. A water-cooled chiller rejects heat to condenser water cooled by a cooling tower, which is typically more efficient but adds the tower, condenser pumps and water treatment to maintain.

Does a chiller need a cooling tower?

A water-cooled chiller does, because the tower removes heat from the condenser water. An air-cooled chiller does not, because it rejects heat directly to outdoor air.

What temperature is chilled water?

In comfort cooling systems, chilled water is usually supplied at around 42 to 45°F and returns about 10 to 12°F warmer. Process and low-temperature systems can run colder, often with glycol added.

Related Terms

Want to Learn More?

Explore how Syyclops uses these concepts to transform your infrastructure with digital twin technology.